The BS-03 is an Infrared Sensor Technology based type gas detector with smart transmitter. The sensor is integrated to the transmitter having digital LCD-LED display This detec-tor uses high-performance infrared components and micro-control technology, combined with sophisticated SMD process manufacturing. It has good repeatability, temperature and humidity characteristics, as well as long service life and convenient operation.

The output signal of the detector is 4-20mA standard signal with optional HART.

Besides Infrared Sensor the BS-03 is also available with Plug in SMART Sensors for Point Infrared, VOC's, Toxic's, Oxygen and Catalytic Combustion. These sensors are replaceable type and can be replaced without any special tools.


FEATURES & BENEFITS

Infra-Red Sensor
Double beam infrared technology, dual compensated, Non-Dispersive IR (NDIR) with temperature compen-sation for excellent stability and minimal drift.

Output Choice
4-20mA
RS-485
HART over 4-20mA (Optional)

Digital Display
LED-LCD Display
No Backlight Required
Can be seen from Wide Distance

Optics
Dirty Optics warning with correct Operation upto 70-80% for NDIR Sensor.
Easy Cleaning of Mirror or Sensor Replacement

Other Features
Relay outputs for Alarm and Faults
Non-Instrusive Calibration
Intrinsically Safe HART Port (Optional)
Smart Sensor modules for Point IR, Toxics and VOC's


SPECIFICATIONS

Dimensions 210mm x 200mm x 105mm
Weight < 2 Kg
Enclosure Material Cast Aluminium Alloy or SS-316
Sensor Housing Material SS-316
Ingress Protection IP-66
Cable Entry Two 3/4" NPT
Power 18-30VDC < 2W
Electrical Output 4-20mA Current Sink or Source RS-485 MODBUS RTU
HART over 4-20mA Signal
Display Main Display: LED-LCD (Red) Indicators: Alarm 1, Alarm 2, Fault
Relays 2 Configurable Relays 5A@230VAC
5A@30VDC
Intrinsically Safe HART Port Optional
Sampling Method Natural Diffusion with Chimney Effect
Working Temperature -400C to +70°C
Working Humidity 0-95% RH (no dews)
Accuracy ± 1% for 0-100% range (NDIR)
± 2% to ± 3% for 0-100% range (TOXICS)
Repeteability ± 2% FSD
Warm-up Time NDIR/Catalytic - 120 seconds Toxics - 60 seconds
Zero Drift ± 2% FSD per year maximum
Approvals ATEX - Ex dB IIC T6 Gb PESO
Testing EN 60079-0: 2012 EN 60079-1: 2014 SIL2
The NDIR Sensor is configurable fo1-C12 Hydrocarbons

SENSON RANGES

TARGET GAS RANGE RESOLUTION SENSOR TYPE RESPONSE TIME
CH4 0~100% LEL 1% LEL Catalytic Combustion/
Non-Dispersive IR
T90 < 30 Sec (Cat)
T90 < 3 Sec (NDIR)
0~5% VOL 0.01% VOL
0~100% VOL 1% VOL
C3H8 0~100% LEL 1% LEL
H2 0~100% LEL 1% LEL Catalytic Combustion T90 < 15 Sec
0~1000 ppm 1 ppm Electrochemical  T90 < 10 Sec
CO2 0~5% VOL 0.01% VOL Non-Dispersive IR T90 < 3 Sec
0~6000 ppm 1 ppm Non-Dispersive IR T90 < 3 Sec
C4H10 0~100% LEL 1% LEL Catalytic Combustion/
Non-Dispersive IR
T90 < 30 Sec (Cat)
T90 < 3 Sec (NDIR)
CO 0~1000 ppm 1 ppm Electrochemical  T90 < 10 Sec
0~500 ppm 1 ppm Electrochemical  T90 < 10 Sec
H2S 0~100 ppm 1 ppm Electrochemical  T90 < 10 Sec
0~30 ppm 1 ppm Electrochemical  T90 < 10 Sec
O2 0~30% VOL 0.1% VOL Electrochemical  T90 < 10 Sec
NH3 0~100 ppm 1 ppm Electrochemical  T90 < 10 Sec
0~1000 ppm 1 ppm Electrochemical  T90 < 10 Sec
SO2 0~100 ppm 1 ppm Electrochemical  T90 < 10 Sec
Cl2 0~20 ppm 0.1 ppm Electrochemical  T90 < 10 Sec
VOC 0~1000 ppm 1 ppm PID T90 < 10 Sec
NO2 0~100 ppm 1 ppm Electrochemical  T90 < 10 Sec
ETO 0~100 ppm 1 ppm Electrochemical  T90 < 10 Sec
HCN 0-100 ppm 1 ppm Electrochemical  T90 < 10 Sec

The NDIR Sensor is configurable for C1-C12 Hydrocarbons


Download Catalogue