UV/IR Flame Detector

Specifications

  • Type : Ultraviolet and Infrared
  • Detection Range : 100ft(30m(FM), 15m(KFI)) for N-Heptane fire
  • Field of View : Horizontal 90°, Vertical 90°
  • Temperature Range Operating : -40℃ to +75℃
  • Storage : -50℃ to +80℃
  • Humidity Range : 0 to 95% relative humidity
  • Explosion proof :
    • Class I Division 1 Groups B,C and D(FM)
    • Class II Division 1 Groups E,F and G(FM)
    • Class III (FM)
    • Ex db IIB+H2 T6(ATEX, KGS)
  • Output
    • Relay
      • Fire Alarm, Fault Alarm, Warning Alarm
      • From A or B Selectable, 28vdc, 2A
    • 4-20mA
    • RS-485

Structure

  • Dimensions : W134 x H117 x D120 (mm)
    • W5.3 x H4.6 x D4.7 (inch)
  • Enclosure Material : Stainless steel 316
  • Shipping Weight : 3.4 kg
  • Color : Metal
  • Conduit Entry Size : 2 x 1/2 inch PF

Electrical

  • Operating Voltage : Typical DC24V (17 to 32)
  • Power Consumption : 1.8W maximum at 32 vdc
  • Wiring : 14AWG(2.08mm2) to
    • 24AWG(0.205mm2) shield
    • cable recommended.
  • Electromagnetic Compatibility : EMC Protected